Product : ISaGRAF V3
Date : 17-December-1999
File : Tracing the communication.htm
Subject : How to activate more traces
Keywords: trace - communication - isa.ini
____________________________________________________________________
In the case of RS232 communication, the beginning of sent and
received frames are displayed in the ISaGRAF Trace window, if it is
opened before launching the ISaGRAF debugger.
Useful traces including frame headers are also displayed in the
ISaGRAF Trace window in the case of ETHERNET communication.
In the case of RS232 communication, many other detailed messages can
be displayed directly in the ISaGRAF debugger message window
(with run-time errors) if the following entry is set in the
ISA.INI file:
[DEBUG]
ComTrace=1
Some more trace in the debugger
From the projet manager, hit "Ctrl+T" to have some traces
displayed in the error list. Traces are related to exchanges between
the communication server and the client applications
(list of variables to be refreshed, update notifications…)
____________________________________________________________________